Installation notes for mounting the 5385AGS (side) or B (back) Reader
1. The MultiProx Reader must be located a minimum of 6 inches (15.3cm) away from electrical wiring, conduit,
metal wall studs or metal pipes.
2. The MultiProx Reader must be located a minimum of 2 inches (5.08cm), on all sides, away from any metal
objects. This includes rebar, metal mesh, sheet metal, or metal beams.
3. Mounting the MultiProx Reader in an enclosure is acceptable, provided a minimum of 3 inches (7.62cm)
clearance is maintained on all sides.
4. Insulate all cable connectors with electrical tape or shrink tubing so contact is not made with any metal or
conductive material.
5. The MultiProx Reader should not be mounted within six feet of any monitors (VDTs or CRTs) . The scan
frequencies of most monitors may interfere with the signal received from the access control cards. Motors and
electronic devices generate RF noise that may interfere with the reception of the signal from an access control
card. The effect of RF noise is typically a reduction of read range. The MultiProx is susceptible to RF
interference as are all devices that receive RF signals, such as, radios, television or cellular phones. See also
MultiProx Reader Installation Guide 5385-900-01.
MultiProx Reader Dimensions - Figure 6